How to Update Firmware in TIA Portal
This guide shows you how to update firmware in TIA Portal for an S7-1500 CPU. You check the network connection to the PLC, download the correct firmware from Siemens, load it with the Firmware loader, and verify the new version. The guide also covers the offline method that uses a SIMATIC Memory Card.
Video: TIA Portal: Firmware Updates - How and Where? Here! by Hegamurl. All credit for the demonstration goes to the creator; watch the original on YouTube. The written guide below was generated from this video by Docsie. Creator? Request a change or removal.
This guide shows you how to update firmware in TIA Portal for an S7-1500 CPU. You check the network connection to the PLC, download the correct firmware from Siemens, load it with the Firmware loader, and verify the new version. The guide also covers the offline method that uses a SIMATIC Memory Card.
Prerequisites
Before you start, make sure you have the following:
- TIA Portal installed on your PC. You don't need to open a project to perform a firmware update.
- A PLC that is reachable on your network. Your PC and the PLC must be on the same subnet.
- A Siemens Industry Online Support account to download firmware. Account creation may require manual verification and can take one or two days.
- Your PLC's article number, for example
6ES7 516-3AN00-0AB0. - For the offline method only: a SIMATIC Memory Card (SMC) and, if your PC has no memory card slot, an external USB card reader.
Check the connection to your PLC
Step 1: Open TIA Portal
Launch TIA Portal on your PC. The main window opens with no project loaded, and the left panel shows Online access and Card Reader/USB memory.

Step 2: Find your PLC under Online access
In the Project tree, expand Online access. This section lets you connect to PLCs and other devices on your network.
Expand your network interface (for example, "DisplayLink Network Adapter NCM") to see the connected devices. Your PLC is listed with its IP address, for example "firmware.profinet interface_1 [192.168.2.1]". Confirm that the PLC is visible and accessible.

Step 3: Check network compatibility
Make sure your PC is on the same subnet as the PLC. For example, if the PLC IP address is 192.168.2.1 and the subnet mask is 255.255.255.0, your PC's IP address must also start with 192.168.2.x.
If the subnet or the first three numbers of the IP address don't match, you have limited access to PLC features.
Step 4: Open Online & diagnostics
Right-click the PLC node, or expand it, and select Online & diagnostics. This opens a detailed diagnostics view with multiple diagnostic points and device information.
You see all diagnostic options only if your PC is correctly networked with the PLC.
Step 5: Verify the PLC network settings
In the diagnostics view, select the PROFINET interface [X1] node and review the IP parameters:
- IP address:
192.168.2.1 - Subnet mask:
255.255.255.0
Confirm that these settings match your PC's network configuration.
Step 6: Verify your PC's IP address
The first three numbers (octets) of your PC's IP address and subnet mask must match those of the PLC, for example 192.168.2.x and 255.255.255.0. If you're unsure of your PC's IP address, check it as follows:
- Press the Windows key, type
CMD, and press Enter to open the Command Prompt. - Type
ipconfigand press Enter. - Find the network adapter you are using, for example the Ethernet adapter.
- Read the
IPv4 Addressline (for example,192.168.2.41) and theSubnet Maskline (for example,255.255.255.0). - Confirm that the first three octets match the PLC's network (for example,
192.168.2).
Your PC may have multiple IP addresses. Use the one that belongs to the correct network adapter.
Step 7: Assign or change the PLC IP address (if needed)
If your PC and PLC aren't on the same subnet, use the Assign IP address function:
- In the diagnostics view, under Functions, select Assign IP address.
- Enter a compatible IP address (for example,
192.168.2.1) and the subnet mask (255.255.255.0). - Click Assign IP address to apply the changes.

Check the current firmware version
Step 8: Open the Firmware update function
With your PLC selected under Online access, expand Functions in the diagnostics view and click Firmware update. You see options to update the PLC, local modules, or the display. For this example, select PLC to update the main controller.
The current firmware version, for example V1.8.1, is displayed. Firmware updates can improve safety and add new features. Keeping firmware up to date is recommended, but if you have no specific need, updating is optional.

Download the firmware
Step 9: Open the Siemens Industry Online Support website
Open the Siemens Industry Online Support page for firmware updates, and make sure you're logged in to your Siemens account. If you don't have an account, create one first.
The page provides:
- Download links for the latest firmware versions for S7-1500 CPUs, displays, and ET 200 CPUs.
- Descriptions and compatibility information for each firmware version.
- A table listing article numbers and their corresponding firmware versions.
Download requests may require manual verification and can take one or two days to process.
Step 10: Review the firmware update page
The page lists many components that are eligible for firmware updates. Scroll down to find detailed information about each firmware version, including the changes or improvements it introduces. Differences between versions are described in the lower section of the page.

Step 11: Locate the firmware for your PLC
The page you opened is specific to S7-1500 CPUs. For a different device, enter your PLC's article number in the search field at the top of the page to filter the results.
To find your article number in the list:
- Press
Ctrl + Fto open the browser's search function. - Type or paste your article number, for example
6ES7 516-3AN00-0AB0. - Press Enter to jump to it in the list.
Step 12: Choose the firmware version
Review the firmware versions available for your article number, for example V1.8.2, V1.8.4, and V1.8.5, and note the latest one. The newest version is generally recommended unless you have a specific need for an older one.

Step 13: Verify the article number
Double-check that the highlighted article number matches your PLC's model. Multiple entries may exist for similar models, so always select the exact match for your hardware. Then continue to the download.

Step 14: Download the ZIP archive
Click the download link for your article number and the version you want, for example 6ES7516-3AN00-0AB0_V185.ZIP. Save the ZIP file to your computer.
Step 15: Extract the ZIP archive
Right-click the ZIP file on your desktop and select Hier entpacken (Extract here), or a similar extraction option.

Load the firmware with the Firmware loader
Step 16: Open the Firmware loader and browse for the file
In TIA Portal, go to Online & diagnostics for your PLC and select Firmware update. In the Firmware loader section, click Browse to locate the extracted firmware file.
Step 17: Open the extracted firmware folder
In the file browser dialog, go to the folder where you extracted the firmware files, for example the FWUPDATE.S7S folder on your desktop. Open the folder to view the available firmware files.
Step 18: Select the firmware file for your CPU
Choose the file that matches your article number and version, for example 6ES7 516-3AN00-0AB0 V01.08.05.upd. Click Open to load it into the Firmware loader.
Step 19: Confirm the version and compatibility
The Firmware loader displays the selected file and its version, for example V1.8.5. If your current firmware is older, for example V1.8.1, proceed with the update.
If the selected firmware isn't compatible with your local modules or displays, TIA Portal displays a warning and prevents the update. Always verify that the firmware file matches your CPU's article number and hardware version.
Step 20: Run the update
Click Run update in the Firmware loader. When TIA Portal asks "To load the firmware file, the operating mode of the CPU must set to STOP.", click Yes to set the PLC to STOP mode.
Step 21: Wait for the update to finish
Monitor the progress bar in the Firmware update dialog. It shows the progress percentage and the estimated remaining time in seconds, for example "72% completed, Remaining time in seconds: 7". Don't interrupt the process until it finishes.

Step 22: Start the module
When the update completes, TIA Portal displays a confirmation: "The firmware V1.8.5 was transferred successfully to module Firmware [192.168.2.1] with article number 6ES7 516-3AN00-0AB0. This firmware was activated on the module. The module is in STOP. Do you want the module to start now?"
Click Yes to start the module. Check the CPU operator panel to make sure the module changes from STOP to RUN mode.

Update firmware offline with a SIMATIC Memory Card
Step 23: Open the Siemens update documentation
You can also update firmware without an online connection. Open the Siemens support page "Description of Firmware Update for S7-1500 CPU, Displays, ET 200SP CPUs and ET 200pro CPUs".
Review the "Online firmware update with STEP 7 (TIA Portal)" section. The documentation outlines prerequisites, online update steps, and offline update procedures.
Step 24: Prepare the SIMATIC Memory Card
The SMC is not a standard SD card. It is a dedicated SIMATIC Memory Card. To update offline:
- Download the update file for your CPU.
- Insert the SMC into the SD card reader of your programming unit or computer.
- Copy the firmware update files onto the SMC as described in the documentation.
- Insert the SMC into the CPU to start the update.
The documentation highlights this procedure in the section "Offline firmware update with the SIMATIC Memory Card (STEP 7, TIA Portal)".

Step 25: Use an external card reader if needed
If your PC has no memory card slot, use an external card reader:
- Connect the card reader to your PC through USB.
- Insert the SIMATIC Memory Card into the reader.
- Copy the required firmware files from your desktop to the SMC.
- Remove the SMC from the reader and insert it into the CPU to perform the update.

Verify the updated firmware
Step 26: Check the firmware version in Online data
In TIA Portal, check the Online data section for the CPU. Confirm that the Firmware field shows V1.8.5 and that the article number matches your device, 6ES7 516-3AN00-0AB0.
Hover over the firmware version if you need more details. A tooltip may appear with module compatibility information.

Step 27: Finish the update and save your project
Confirm that the Firmware loader section is idle and its status field is empty. The Run firmware after update checkbox should be unchecked if you need no further updates. Save your project if you made any changes.
Step 28: Close TIA Portal
If you need no further configuration, close the TIA Portal application.

What's next
Always verify the firmware version and article number after an update. For additional questions or troubleshooting, consult the Siemens Industry Online Support documentation.
Summary
To update firmware in TIA Portal, you:
- Confirm that your PC and PLC are on the same subnet, using
192.168.2.1and255.255.255.0as the example values. - Check the current firmware version under Firmware update.
- Download and extract the correct firmware ZIP for your article number from Siemens Industry Online Support.
- Select the
.updfile in the Firmware loader, click Run update, and confirm the switch to STOP mode. - Start the module when the update completes and verify the new version under Online data.
If you prefer, you can perform the update offline with a SIMATIC Memory Card.
Generation details: cost, quality tiers
Docsie billed 4,500 credits ($3.15) to analyze this 9-minute video at standard quality. The rewrite, template fill and Word/PDF exports were included. The same video at each quality tier:
| Quality | Frames sampled | Credits | Approx. cost |
|---|---|---|---|
| Draft | every 16-30 s | 2,250 | $1.57 |
| Standard (this guide) | every 8-15 s | 4,500 | $3.15 |
| Detailed | every 4-7 s | 9,000 | $6.30 |
| Ultra | every 1-3 s | 18,000 | $12.60 |
Credits priced at $0.70 per 1,000; plans include a monthly allowance. Enterprise customers on on-premise or bring-your-own-model deployments run this on their own inference and pay no per-video credits.
Generated by Docsie Video-to-Docs on 2026-11-24 from a 8-minute video. Screenshots are frames from the source video and belong to their creator, Hegamurl, whose original is embedded above. If you own this video and want the guide removed or credited differently, contact us and we will act within one business day.