How to Create Produced and Consumed Tags in Studio 5000
This guide shows how to create produced and consumed tags in Studio 5000 so that two ControlLogix controllers can exchange data over EtherNet/IP. The screens shown are from RSLogix 5000. You set up a produced tag in the producer controller, add the producer to the consumer's I/O Configuration, create a matching consumed tag, and then confirm that the value transfers.
Video: How to configure a Produce and Consume Tag in RSLogix5000 by Robotics & Automation - Electro-Mechanical (2012). All credit for the demonstration goes to the creator; watch the original on YouTube. The written guide below was generated from this video by Docsie. Creator? Request a change or removal.
This guide shows how to create produced and consumed tags in Studio 5000 so that two ControlLogix controllers can exchange data over EtherNet/IP. The screens shown are from RSLogix 5000. You set up a produced tag in the producer controller, add the producer to the consumer's I/O Configuration, create a matching consumed tag, and then confirm that the value transfers.
Prerequisites
Before you start, make sure you have the following:
- An RSLogix 5000 project named "Producer" configured for a 1756-L61 processor, with the processor in Run mode and all modules (input, output, analog, and network cards) properly connected.
- A 1756-ENBT/A Ethernet/IP card in the producer's I/O Configuration for network communication.
- A second RSLogix 5000 project for the consumer controller. Its processor type can be the same (for example, 1756-L61), but its I/O tree differs from the producer's.
- The IP address, Ethernet card slot number, chassis size, and revisions of the producing PLC.
Part 1: Review the producer program
Step 1. Open the Producer project
Launch RSLogix 5000 and open the "Producer" project. The left pane lists the controller, tasks, data types, and I/O modules, including the 1756-ENBT/A Ethernet card. The right pane shows the ladder logic with a push button (PB_1), a counter (Counter_1), and a move instruction that transfers the counter's accumulated value to Produced_Tag_1.

Step 2. Verify the network configuration
In the I/O Configuration tree, confirm that these modules are present:
- 1756-L61 Producer (controller)
- 1756-IB16 Input
- 1756-OB8 Output
- 1756-IF4FXOF2F/A Analog
- 1756-ENBT/A Ethernet_T3 (Ethernet/IP card)
Also confirm in the status bar that the Ethernet module is configured and running.
Step 3. Inspect the ladder logic that feeds the produced tag
Examine the main routine:
- The first rung contains the push button PB_1 input (
Local:1:I.Data.0). It increments Counter_1, which has a preset of 40 (the accumulated value in the example is 38). - The second rung uses a MOV (Move) instruction. The source is
Counter_1.ACC(value 38) and the destination isProduced_Tag_1.
Hover over or right-click the Produced_Tag_1 destination to view its details. In this example, the tag is a DINT with Controller scope and a value of 38.

Part 2: Create the produced tag
Step 4. Open the produced tag properties
Right-click Produced_Tag_1 in the ladder logic or the tag browser. Then select Edit "Produced_Tag_1" or Properties from the context menu.

Step 5. Configure the produced tag
First, choose a data type that works for produced and consumed tags:
- DINT (Double Integer) is the most common data type.
- REAL or FLOAT are optional if your application requires them.
- Boolean tags cannot be produced or consumed directly. To exchange Boolean data, create a User-Defined Data Type (UDT) and include the Boolean within it.

In the Tag Properties dialog, enter the following:
- Name: Produced_Tag_1
- Type: Produced (select it from the drop-down menu)
- Data Type: DINT
- Scope: Producer (controller scope)
- Style: Decimal
Click Connection... to configure consumer settings. Under Connection, set the number of consumers to 1 if only one other processor will consume this tag.

Click OK or Apply to save the settings. The tag is now a produced tag, ready for consumption by another controller.
Part 3: Prepare the consumer controller network
Step 6. Open the consumer controller project
Open the RSLogix 5000 project for the consumer controller (example name: RSLogix 5000 Consumer). In the consumer's main routine, locate the rung that uses the consumed tag (for example, Consumed_tag_2).
In this example, an EQU (Equal) instruction compares Consumed_tag_2 (value 39) to a constant (32). The logic can also include MSG (Message) and MOV (Move) instructions for other data handling.

Step 7. Add a new module under the Ethernet card
In the consumer's I/O Configuration tree, find the Ethernet module (for example, 1756-ENBT/A EtherNet_Module). You use this module to establish the connection to the producer PLC.

Right-click the Ethernet module and select Add New Module.

Step 8. Configure the network module for the producer PLC
In the Select Module dialog, choose the Ethernet module type that matches the producer PLC's Ethernet module (for example, 1756-ENBT/A) from the list under Communications. Click OK.

In the New Module dialog, enter the following:
- Name: A descriptive name for the module (for example,
EtherNet_Module). - Description: Optional.
- Slot: The slot number of the network card in the producing PLC (for example,
0). - Chassis Size: The chassis size of the producing PLC (for example,
17). - Revision: The correct module revision (for example,
4.1). - IP Address: The IP address of the producing PLC.
- Electronic Keying: The keying method (for example,
Compatible Keying).
Do not enter the IP address of the consumer PLC. Use the address of the PLC you want to receive data from. Click OK to add the module, or cancel if you are only demonstrating the process.
After you add the module, RSLogix 5000 automatically adds the backplane for the producing PLC. You then see the network card and backplane under the Ethernet module in the I/O tree.
Step 9. Add the remote controller module
Right-click the new backplane under the producer PLC's Ethernet module and select New Module. In the Select Module dialog, choose the controller type that matches the producing PLC (for example, 1756-L61).

When prompted, select the major revision for the controller (for example, 17).

In the New Module dialog for the controller, enter the following:
- Name: A name that is meaningful for your project. It does not have to match the name on the producer PLC.
- Slot: The slot where the controller is installed on the remote system (for example,
1). - Description: Optional.
- Revision: Confirm the revision (for example,
17.1).
Click OK to add the controller module, or Cancel if you are only demonstrating the process.
The backplane and controller now appear in the I/O Configuration tree, which confirms the setup.
Part 4: Create the consumed tag
Step 10. Edit the consumed tag properties
Locate the consumed tag (for example, Consumed_tag_2) in the ladder diagram. Right-click it and select Edit "Consumed_tag_2" Properties.

In the Tag Properties window:
- Enter a name that makes sense for your application (for example,
Consumed_tag_2). - Optionally, add a description.
- Set Type to
Consumedfrom the drop-down menu. - Make sure Data Type matches the producer tag (for example,
DINT).
Step 11. Configure the consumed tag connection
Click Connection... next to the Type field. In the Consumed Tag Connection window, set the following:
- Producer: Select the producer from the drop-down (for example,
Producer_PLC). - Remote Data: Enter the exact name of the producing tag on the remote PLC (for example,
Produced_Tag_1). - RPI (Requested Packet Interval): Set as needed (for example,
20.0 ms). - Use Unicast Connection over EtherNet/IP: Optionally select it if your network setup requires it.

Step 12. Save the consumed tag
Click OK in the Consumed Tag Connection window. Then click OK in the Tag Properties window to save your changes.

Step 13. Confirm the consumed tag in your logic
Confirm that the consumed tag is now used in your logic. In this example, Consumed_tag_2 is Source A in an EQU (Equal) instruction, compared to a fixed value (for example, 33).
Hover over the tag to see its data type (DINT), scope (Controller), and current value (for example, 33).

Part 5: Verify the data transfer
Step 14. Check the producer tag operation
Make sure you are online with the producer controller. When you toggle the PB_1 bit from its context menu, the counter's accumulated value increments. The MOV instruction then transfers that value to the produced tag (Produced_Tag_1).

Step 15. Go online with the consumer controller
Switch the consumer controller to Run mode if it is not already online. Observe the logic in real time. The consumed tag value updates as data arrives from the producer PLC.
In this example, Consumed_tag_2 is 39 and the EQU instruction compares it to 32.

Step 16. Compare the producer and consumer values
In the Producer window, find the rung containing the CTU (Count Up) instruction. Confirm that the Accum value for Counter_1 is 39, and that the MOV instruction moves Counter_1.ACC (39) to Produced_Tag_1.
In the Consumer window, verify that the EQU instruction uses consumed_tag_2 as Source A with a value of 39, and that Source B is 32. The tooltip confirms the value of consumed_tag_2 is 39. Adjust the window sizes as needed so both sets of logic are visible.

Step 17. Confirm the remote update
As the value in the producer PLC changes, confirm that consumed_tag_2 in the consumer PLC updates accordingly. In this example, consumed_tag_2 becomes 40, matching the updated Produced_Tag_1. The EQU instruction now compares 40 to 32.

Summary
To create produced and consumed tags in Studio 5000, you complete these tasks:
- Set the producer tag's Type to Produced, use a DINT data type (or a UDT for Boolean data), and set the number of consumers in Connection....
- In the consumer project, add the producing PLC's Ethernet module, using the producer's IP address, slot, chassis size, and revisions.
- Add the remote controller under the new backplane. Its name is user-defined and does not need to match the producer's actual name.
- Set the consumed tag's Type to Consumed, match the producer's data type, and enter the exact remote tag name in Remote Data.
- Go online and confirm that the consumed tag value matches the produced tag value as the producer value changes.
Generation details: cost, quality tiers
Docsie billed 4,000 credits ($2.80) to analyze this 8-minute video at standard quality. The rewrite, template fill and Word/PDF exports were included. The same video at each quality tier:
| Quality | Frames sampled | Credits | Approx. cost |
|---|---|---|---|
| Draft | every 16-30 s | 2,000 | $1.40 |
| Standard (this guide) | every 8-15 s | 4,000 | $2.80 |
| Detailed | every 4-7 s | 8,000 | $5.60 |
| Ultra | every 1-3 s | 16,000 | $11.20 |
Credits priced at $0.70 per 1,000; plans include a monthly allowance. Enterprise customers on on-premise or bring-your-own-model deployments run this on their own inference and pay no per-video credits.
Generated by Docsie Video-to-Docs on 2026-11-24 from a 7-minute video. Screenshots are frames from the source video and belong to their creator, Robotics & Automation - Electro-Mechanical, whose original is embedded above. If you own this video and want the guide removed or credited differently, contact us and we will act within one business day.