How to Change the IP Address in Studio 5000
This guide explains how to change the IP address in Studio 5000 for a 1756-ENBT/A Ethernet module, and how to reconnect to the controller afterward. The screens shown use the RSLogix 5000 interface. You change the address in the module properties, download the change, apply the live address, and then update the communication path in RSWho.
Video: How to change the Ethernet IP address in RSLogix5000 project (ENBT-card) by Robotics & Automation - Electro-Mechanical (2012). All credit for the demonstration goes to the creator; watch the original on YouTube. The written guide below was generated from this video by Docsie. Creator? Request a change or removal.
This guide explains how to change the IP address in Studio 5000 for a 1756-ENBT/A Ethernet module, and how to reconnect to the controller afterward. The screens shown use the RSLogix 5000 interface. You change the address in the module properties, download the change, apply the live address, and then update the communication path in RSWho.
Prerequisites
Before you begin, make sure you have the following:
- An RSLogix 5000 project loaded and an online connection to the controller.
- A new IP address that no other device on the network uses.
- Only the last octet changes. The network portion (for example,
192.168.1) stays the same, as set by the subnet mask.
Verify online status and go offline
Verify you are online with the controller
Open RSLogix 5000 and load your project. Confirm you are online with the controller:
- The status indicators show "Run Mode", "Controller OK", "Battery OK", and "I/O OK" in green.
- The top bar displays "Rem Run", and the path shows the current Ethernet/IP driver (for example,
AB_ETHIP-1\192.168.1.211\Backplane\0). - The project tree and program logic are accessible.

Go offline with the controller
Switch RSLogix 5000 to offline mode before you make changes. Confirm the status bar now shows "Offline".
Change the IP address in the module properties
Open the Ethernet module properties
- In the project tree under "I/O Configuration", locate the 1756-ENBT/A Ethernet module (for example,
[4] 1756-ENBT/A Ethernet_T3). - Right-click the Ethernet module.
- Select Properties from the context menu.

Change the IP address in the General tab
If you need to connect a different PLC to the same network, each device must have a unique IP address. Change only the last octet (for example, .211) to avoid conflicts.
- In the "Module Properties" window, make sure you are on the General tab.
- Under "Address / Host Name", select IP Address.
- Change the last octet from
211to222, so the address becomes192.168.1.222.
Do not change the first three octets (192.168.1). They designate the network portion.

Apply and confirm the change
Click Apply to save the new IP address in the general properties. Then click OK to close the Module Properties window.
Download the changes to the controller
Start a download to apply the configuration changes to the controller. A warning dialog confirms the download and warns about possible motion or configuration mismatches. Click Download to proceed.
At this stage, the change is reflected only in the general properties. The live IP address on the Ethernet/IP card stays the same until you update it in the Port Configuration tab. The current communication path (for example, AB_ETHIP-1\192.168.1.211\Backplane\0) is still valid.

Update the live IP address
Reopen the module properties
The IP address appears in two places in the module properties:
- The General tab, which you can edit only while offline.
- The Port Configuration tab, which reflects the live module setting when online.
After the download, right-click the 1756-ENBT/A Ethernet module again in the I/O Configuration tree and select Properties. The IP address field in the General tab is now grayed out because it is not editable while online.
Open the Port Configuration tab
Click the Port Configuration tab. It shows the current live IP address of the module (for example, 192.168.1.211). This is the address active on the Ethernet/IP card, and it is typically the number scrolling across the card's display.

Prepare to change the live IP address
Changing the IP address in the Port Configuration tab immediately affects the module's network identity. Once you apply the change, the current communication path becomes invalid. RSLogix 5000 does not update the path automatically. You lose the connection and must reconnect using the new IP address.
Keep the following in mind:
- Make sure you have the correct new IP address and that no other device on the network uses it.
- Be prepared to re-establish communication with the module at its new IP address.
Set the new IP address
In the Port Configuration tab, RSLogix 5000 may warn that the communication settings do not match between the General tab and the Port Configuration tab. This warning is expected when the IP address values differ between the two tabs.
Verify the new IP address (192.168.1.222) is entered, then click Set to apply it to the module.

Acknowledge the address change warning
A dialog box warns that changing the IP address may cause a loss of connectivity. It also warns that other controllers could be affected if they share the module. The warning reads:
- "DANGER. Multi-controller systems. If two or more controllers are sharing this module, applying these configuration changes could affect the operation of the other controllers."
- "DANGER. IP Address change. Operation may interrupt control."
- "Apply the changes to the module configuration?"
Click OK to proceed.

Wait for the address change to complete
The software attempts to apply the new IP address. Expect a delay while the module updates and the connection is lost because of the address change. The warning dialog may stay visible for several seconds.

Acknowledge the loss of communication
After the address change, RSLogix 5000 displays a message that it can no longer communicate with RSLinx and has been taken offline. The message reads:
- "Can't communicate with RSLinx. RSLogix 5000 has been taken offline."
- "If online operations are in progress, they will not be completed."
- "Offline operations after communication loss will result in loss of correlation. To avoid loss of correlation, close views without applying changes before attempting to go online."
Click OK to close the message.

Confirm the project is offline
The status bar and module properties now indicate "Offline". The IP address fields in the Port Configuration tab are grayed out and not editable. Click OK to close the Module Properties window.

Update the communication path
Open RSWho
The main RSLogix 5000 window shows the project as offline. The current communication path (for example, AB_ETHIP-1\192.168.1.211\Backplane\0) still points to the old IP address, which is no longer valid.
Open the "Who Active" (RSWho) dialog to browse the available network connections. The dialog still displays the old connection (192.168.1.211), which is now invalid. You need to select the new IP address (192.168.1.222) to re-establish communication with the module.
Wait for the hourglass to disappear
After you start a network browse or connection, an hourglass icon appears on the RSLogix 5000 interface. It indicates that the software is processing and may remain visible for a while. Do not take further actions until the hourglass disappears.

Browse through the AB_ETHIP driver
When the hourglass disappears, the device tree in the "Who Active" dialog becomes interactive. Browse through the AB_ETHIP-1, Ethernet driver to find the processor you just configured. Expand the network tree to view all connected controllers and devices.

Confirm all controllers appear
Check that all expected controllers, including the newly configured one, appear in the device list. The network tree should display all detected devices and their IP addresses.

Clear the project path if needed
If you need to reset the browsing context, click Clear Project Path in the "Who Active" dialog. This clears the current selection and lets you start a new browse session. Wait for the status to update, confirming the path is cleared.

Collapse the network tree
To tidy the view or disconnect from a device, click the minus sign (-) next to the AB_ETHIP-1, Ethernet driver. This collapses the network tree and hides the list of connected devices.
Wait for automatic device discovery
Allow the software to rediscover devices on the network automatically. This can take up to a minute, depending on network size and traffic. The device list repopulates when discovery is complete.

Expand the network tree to verify browsing
Click the plus sign (+) next to the AB_ETHIP-1, Ethernet driver to expand the network tree again. Confirm that all controllers and devices are visible and correctly listed.

Reconnect at the new IP address
Identify disconnected devices
In the "Who Active" dialog, devices that are no longer accessible, whether from disconnection or network issues, show a red X next to their IP addresses and device names. This helps you quickly see which devices are unreachable. In the example, these devices show red Xs:
- 192.168.1.200, PowerFlex 40, PowerFlex 40 IP 110V .50HP
- 192.168.1.201, 1756-ENBT/A, 1756-ENBT/A
- 192.168.1.211, 1756-ENBT/A, 1756-ENBT/A
- 192.168.1.222, 1756-ENBT/A, 1756-ENBT/A
- 192.168.1.195, PowerFlex 40, PowerFlex 40 IP 110V .50HP
- 192.168.1.7, MicroLogix1100, 1763-L16BWA B/9.00
- 192.168.1.9, PanelView Plus 600, PanelView-Plus

Select the processor at the new IP address
Locate a processor that is available for connection and not marked with a red X. Click the plus sign (+) next to the processor's IP address to expand its backplane. In this example, you select and expand 192.168.1.222, 1756-ENBT/A, 1756-ENBT/A.

Go online with the selected processor
After you expand the backplane, select the controller module (for example, 1756-L61 LOGIX5561, Producer). Click Go Online on the right side of the "Who Active" dialog. This starts an online connection with the selected controller.

Verify the project path and online status
Once connected, the project path at the top of the RSLogix 5000 window updates to reflect the new connection (for example, AB_ETHIP-1\192.168.1.222\Backplane\0). Confirm the following:
- The status indicators (Run Mode, Controller OK, Battery OK, I/O OK) are green, which indicates a healthy online connection.
- The "Who Active" dialog shows the connected controller and modules without red Xs.

Review the module properties (optional)
To view or edit the properties of a specific module, such as the Ethernet module, open the "Module Properties" dialog. You can review details such as:
- Type: 1756-ENBT/A 1756 10/100 Mbps Ethernet Bridge, Twisted-Pair Media
- Name: Ethernet_T3
- Slot: 4
- Revision: 4.1
- Electronic Keying: Compatible Keying
- Status: Running
Make any changes you need, then click OK to save.
Summary
You now know how to change the IP address in Studio 5000. You edit the address in the General tab while offline, download the change, and set the live address in the Port Configuration tab. Then you select the new address in RSWho to reconnect. Allow enough time for network discovery, and use the collapse and expand controls to manage your view of the network devices.
What's next
- Confirm that the status indicators are green and the project path shows the new IP address.
- Review the module properties to confirm the module status is Running.
Generation details: cost, quality tiers
Docsie billed 4,000 credits ($2.80) to analyze this 8-minute video at standard quality. The rewrite, template fill and Word/PDF exports were included. The same video at each quality tier:
| Quality | Frames sampled | Credits | Approx. cost |
|---|---|---|---|
| Draft | every 16-30 s | 2,000 | $1.40 |
| Standard (this guide) | every 8-15 s | 4,000 | $2.80 |
| Detailed | every 4-7 s | 8,000 | $5.60 |
| Ultra | every 1-3 s | 16,000 | $11.20 |
Credits priced at $0.70 per 1,000; plans include a monthly allowance. Enterprise customers on on-premise or bring-your-own-model deployments run this on their own inference and pay no per-video credits.
Generated by Docsie Video-to-Docs on 2026-11-24 from a 8-minute video. Screenshots are frames from the source video and belong to their creator, Robotics & Automation - Electro-Mechanical, whose original is embedded above. If you own this video and want the guide removed or credited differently, contact us and we will act within one business day.