Skip to content
✦ Made with Docsie · generated from video

How to Calculate an Arc Flash Boundary

This procedure describes how to calculate an arc flash boundary by first determining the incident energy of an arc flash event using the NFPA 70E Annex D.4.3 formula. The calculation builds on a previously determined arcing current and produces the incident energy value, expressed in cal/cm², that is used for PPE hazard category selection and arc flash boundary determination on equipment labels.

Safety 12 steps 8 screenshots 1365 words Source video 4:59 Generated cost $1.75

Video: Calculate incident energy of arc flash - NFPA 70E by Jonathan Gracey (2018). All credit for the demonstration goes to the creator; watch the original on YouTube. The written guide below was generated from this video by Docsie. Creator? Request a change or removal.

This procedure describes how to calculate an arc flash boundary by first determining the incident energy of an arc flash event using the NFPA 70E Annex D.4.3 formula. The calculation builds on a previously determined arcing current and produces the incident energy value, expressed in cal/cm², that is used for PPE hazard category selection and arc flash boundary determination on equipment labels.

Purpose

This SOP walks you through the NFPA 70E Annex D.4.3 method for calculating incident energy, from the basic formula through the final conversion to cal/cm². Completing this calculation is a required step in determining the PPE hazard category and supporting the arc flash boundary calculation for a piece of electrical equipment.

Scope

This procedure applies to incident energy calculations for equipment such as motor control centers (MCCs) and panel boards in the 0.208–1 kV class, and can be adapted for other equipment types, including switchgear, and for both grounded and ungrounded (high-resistance) systems.

Requirements

Before starting, confirm you have the following information available:

Credit screen showing the presenter's name and copyright information
Credit screen showing the presenter's name and copyright information
  • The previously calculated arcing current (Ia) for the system.
  • The system voltage and the bolted three-phase short circuit current.
  • The NFPA 70E Annex D.4.3 formulas and the constants k1 and k2 for your arc type and grounding configuration.
  • Table D.4.2, for the conductor gap and distance exponent values.
  • The manufacturer's time-current curve for the overcurrent protective device (fuse or circuit breaker).
  • The working distance (D) specified for the equipment.

Steps

1

Review the calculation objective

Confirm that your objective is to calculate the incident energy for an arc flash event, continuing from a previously calculated arcing current. This calculation follows NFPA 70E, Annex D.4.3, section D.3, for incident energy.

Title screen showing "ARC FLASH LABEL CALC" and "Developed by: Octagon Seven"
Title screen showing "ARC FLASH LABEL CALC" and "Developed by: Octagon Seven"
2

Review the basic incident energy formula

Refer to the basic formula for normalized incident energy at working distance:

lg En = k1 + k2 + [1.081 × (lg Ia)] + 0.0011G

  • lg denotes log base 10.
  • En is the normalized incident energy (J/cm²).
  • Ia is the arcing current (previously calculated).
  • G is the conductor gap in millimeters.
  • k1 and k2 are constants based on arc type and system grounding.

Screen displaying the NFPA 70E Annex D.4.3 formula: lg En = k1 + k2 + [1.081 × (lg Ia)] + 0.0011G

3

Identify your system parameters and reference Table D.4.2

For this example, the system is a 480VAC Panel with a bolted three-phase short circuit current of 30,000A. Use the following constants and variables:

  • k1 = -0.792 for open air arcs, or -0.555 for arcs-in-a-box (use -0.555 for a panel board).
  • k2 = 0 for ungrounded/high-resistance systems, or -0.113 for grounded systems (use -0.113 for this grounded system).
  • G = 25 mm, the typical conductor gap for panel boards.
  • Ia = 16 kA, the previously calculated arcing current.

Reference Table D.4.2 for the conductor gap and distance exponent: for MCCs and panels, the typical conductor gap is 25 mm and the distance exponent is 1.641.

Screen showing example system values, formula variables, and Table D.4.2 for conductor gap and distance exponent
Screen showing example system values, formula variables, and Table D.4.2 for conductor gap and distance exponent
4

Substitute values into the formula

Substitute the constants and calculated values into the formula:

lg En = -0.555 + (-0.113) + [1.081 × (lg 16.761)] + 0.0011 × 25

Calculate each term step by step:

  • lg 16.761 ≈ 1.224
  • 1.081 × 1.224 ≈ 1.323
  • 0.0011 × 25 = 0.0275
  • Sum: -0.555 + (-0.113) + 1.323 + 0.0275 ≈ 0.68298

The result is lg En = 0.68298.

Screen showing the formula with substituted values and the calculated log of normalized incident energy
Screen showing the formula with substituted values and the calculated log of normalized incident energy
5

Calculate the normalized incident energy

Remove the logarithm by raising 10 to the calculated power:

En = 10^(0.68298) ≈ 4.81925 J/cm²

This is the normalized incident energy at the working distance for the given system parameters.

6

Apply the full incident energy formula

The value calculated in the previous step is the normalized incident energy, not the actual incident energy at the working distance. To find the actual incident energy (E), use the full formula:

E = 4.184 × Cf × En × [(t / 0.2) × (610^x / D^x)]

  • E = incident energy (J/cm²)
  • Cf = constant factor (1.0 if V > 1kV, 1.5 if V ≤ 1kV)
  • En = normalized incident energy (J/cm²)
  • t = arcing time (seconds)
  • x = distance exponent (from Table D.4.2)
  • D = working distance (mm)

Example substitution:

E = 4.184 × 1.5 × 4.81925 × [(0.0167 / 0.2) × (610 / 455)^1.641]

Screen showing the full incident energy formula with substituted values and constants, including the normalized incident energy and system-specific factors
Screen showing the full incident energy formula with substituted values and constants, including the normalized incident energy and system-specific factors
7

Select the correct constant factor (Cf)

Choose the constant factor based on system voltage:

  • For systems with voltage ≤ 1kV, use Cf = 1.5.
  • For systems with voltage > 1kV, use Cf = 1.0.

In this example, the system voltage is 480V, so set Cf = 1.5.

8

Determine the arcing time (t)

The arcing time (t) is determined by the time-current characteristic of your overcurrent protection device (fuse or circuit breaker).

Safety note: Do not use the bolted three-phase fault current for this calculation. Always use the arcing current (previously calculated as 16.7 kA) to find the trip time from the manufacturer's time-current curve, since the bolted fault current does not represent arc flash conditions. In this example, the trip time for 16.7 kA is 0.0167 seconds, so use t = 0.0167.

Screen showing the formula, constants, and Table D.4.2 for selecting the distance exponent and conductor gap for the system
Screen showing the formula, constants, and Table D.4.2 for selecting the distance exponent and conductor gap for the system
9

Reference the distance exponent and working distance

Use Table D.4.2 to find the distance exponent (x) for your equipment type and voltage class. For a 480V panel (MCCs and panels, 0.208–1 kV):

  • Typical conductor gap: 25 mm
  • Distance exponent: 1.641

Use the working distance (D) specified for your system (in this example, 455 mm).

10

Substitute all values and calculate the incident energy

Substitute all determined values into the formula:

  • Cf = 1.5
  • En = 4.81925
  • t = 0.0167 seconds
  • x = 1.641
  • D = 455 mm

The formula becomes:

E = 4.184 × 1.5 × 4.81925 × [(0.0167 / 0.2) × (610 / 455)^1.641]

Performing this calculation gives a result of E = 4.086 J/cm².

11

Convert incident energy to calories per square centimeter

Convert the result from joules to calories using the conversion factor 1 cal = 4.184 J:

E = 4.086 J/cm² ÷ 4.184 = 0.977 cal/cm²

This cal/cm² value is what you use to determine the hazard risk category for PPE selection and to support the arc flash boundary determination for the equipment label.

Screen showing the final calculation, conversion to calories per square centimeter, and the relevant table for conductor gap and distance exponent
Screen showing the final calculation, conversion to calories per square centimeter, and the relevant table for conductor gap and distance exponent
12

Confirm unit conversion and methodology flexibility

Always convert your final incident energy value to cal/cm², since this is the standard unit referenced in arc flash labeling and PPE requirements.

Note that the NFPA 70E Annex D.4.3 formulas and the previously calculated arcing current allow you to mix and match variables to fit your system:

  • Adapt the constants for grounded or ungrounded systems.
  • Apply the method to different equipment types, such as switchgear or panel boards.
  • Adjust the conductor gap, distance exponent, and working distance for your specific equipment.

This approach is customizable across system configurations, which makes it a reliable choice for calculating incident energy. Other calculation methods are also available in NFPA 70E Annex D.4, and you may select whichever method best fits your system and needs.

Verification and summary

Confirm that you have completed the following before finalizing your arc flash label or safety analysis:

  1. Identified the correct formula and constants for your system (arc type, grounding, conductor gap).
  2. Substituted the arcing current and other values into the normalized incident energy formula.
  3. Calculated the log of the normalized incident energy and converted it to En.
  4. Applied the full incident energy formula with the correct constant factor (Cf), arcing time (t), distance exponent (x), and working distance (D).
  5. Determined arcing time from the arcing current and the manufacturer's time-current curve, not the bolted fault current.
  6. Calculated the final incident energy in J/cm² and converted it to cal/cm² for PPE hazard category determination.
Screen showing the final calculation: En = 10^lg En = 4.81925
Screen showing the final calculation: En = 10^lg En = 4.81925

Additional reference screenshots for the full formula and final calculation:

By following these steps, you can accurately determine the incident energy for arc flash labeling and safety analysis using NFPA 70E Annex D.4.3, which supports correct PPE selection and arc flash boundary determination for your equipment.

Generation details: cost, quality tiers

Docsie billed 2,500 credits ($1.75) to analyze this 5-minute video at standard quality. The rewrite, template fill and Word/PDF exports were included. The same video at each quality tier:

QualityFrames sampledCreditsApprox. cost
Draftevery 16-30 s1,250$0.88
Standard (this guide)every 8-15 s2,500$1.75
Detailedevery 4-7 s5,000$3.50
Ultraevery 1-3 s10,000$7.00

Credits priced at $0.70 per 1,000; plans include a monthly allowance. Enterprise customers on on-premise or bring-your-own-model deployments run this on their own inference and pay no per-video credits.

Generated by Docsie Video-to-Docs on 2026-09-14 from a 4-minute video. Screenshots are frames from the source video and belong to their creator, Jonathan Gracey, whose original is embedded above. If you own this video and want the guide removed or credited differently, contact us and we will act within one business day.

Turn your own training videos into guidesJoin teams that save hours, reduce documentation work and scale training with Docsie.
See Docsie in action. No commitment.

Ready to Transform Your Documentation?

Start creating professional documentation that your users will love